What actuators can control energy-saving lamps?
We got from Spain the following question through Zendesk:
What ACTinBOX is needed to switch energy-saving lights?
Can I use an ACTinBOX Classic or, in the other hand, should I use an ACTinBOX QUATRO? The reply is as follow:
If you are connecting only one light for each output circuit (relay from the ACTinBOX), then you can use any output from your QUATRO or CLASSIC actuators.
If you're going to connect more than one iight for each output circuit (relay from the ACTinBOX) then you must use any QUATRO output, or outputs 3rd and 4th from CLASSIC (from 09AAD0001 serial number), since these outputs relays are also ready for capacitive loads. Under no circumstances use an ACTinBOX MAX6. Thank you very much for using the Zennio Web support.
|