| Question of the week in Zendesk: Minimum Load in Luzen |
|
|
|
| Written by Jesus Arias |
| Friday, 18 December 2009 12:25 |
|
Which is the minimum load for the correct performance of Luzen ONE?
When designing and connecting a load to devices Luzen ONE, it is very usual consulting the maximum load that the Luzen is capable of bearing (400 W). On the contrary, we usually forget to consult which is the minimum load for the correct performance of Luzen ONE. We have received from Spain a question about the strange perfomance that a Luzen was presenting. It dealt with some kind of fluctuation that made the load blinking. When we asked about the load connected to the Luzen we discovered that it consisted of 4 electronic transformers for LEDs, of about 3 W each. A total load of 12 W, when the minimum load that should be connected to the Luzen is 50W. These data can be looked up in the Luzen Datasheet:
|
| Last Updated on Wednesday, 23 December 2009 11:03 |